YUW1 Series 1000A-6300A Air Circuit Breaker universal circuit breaker drawer and fixed ACB 3P/4P

Drawer Air Circuit Breaker
Drawer Air Circuit Breaker
3P Fixed Air Circuit Breaker

UW1 series Air Circuit Breaker(hereinafter referred to as circuit breaker) is applied in distribution network with AC 50HZ ,rated voltage 690V(or below),and rated current 200A-6300A.

Get A Quote PDF

YUW1 Series 1000A-6300A Air Circuit Breaker universal circuit breaker drawer and fixed ACB 3P/4P

Get A Quote PDF

Product Details

It is used to distribute electric energy, protect circuit and power supply from damage of defaults,such as overload,under voltage,short circuit,single-phase grounding.Circuit breaker has intelligent protection function,and its selective protection is accurate.

 

Pole: 3P,4P 

Rated current: 1000A, 2000A, 3200A, 4000A, 6300A

Ue: AC 380V/400V/600V/690V; Ui: 1000V; Uimp: 12kV;

In: 200A, 400A, 630A, 800A, 1000A, 1250A, 1600A;

Type of overcurrent trip: Electronic;

AC 400V: Ics=55kA; Icu=50kA/1s;

AC 480V: Ics=65kA; Icu=85kA/1s;

AC 690V: Ics=42kA; Icu=50kA; Icw=42kA/is;

Selective category: Category B; intended for isolation.

Product standards and technical requirements : GB/T 14048.2-2020.

Product Summary

 

YUW1 series Air Circuit Breaker(hereinafter referred to as circuit breaker) is applied in distribution network with AC 50HZ ,rated voltage 690V(or below),and rated current 200A-6300A. It is used to distribute electric energy, protect circuit and power supply from damage of defaults,such as overload,under voltage,short circuit,single-phase grounding.Circuit breaker has intelligent protection function,and its selective protection is accurate.Besides,it can improve the reliability of power supply and avoid unnecessary blackout.At the same time ,it possesses open-type communication interface to realize four-remote function,namely remote control,remote regulating,remote measurement and remote communication,in order to meet the requirement of control center and automatic system.This circuit breaker has isolation function.

 

Classify

 

1. Accord to install:Fix type,Drawer type.
2. Accord to pole:3P、4P
3. Accord to operation:Electric operation,Manual operation(Repair,maintenance)

 

 

Release

 

Intelligence controller,under-voltage instant(or delayed)release,shunt release.

Product Parameters

Intelligence Controller Function

 

1. intelligence controller:H(intelligence type),M(Standard type)、L(Economy type)

 

2. Have overload long delayed inverse time limit,short delayed inverse time limit,constant time-lag and instant function,it can according to user require to set protect.

 

3. Single ground protect function.

 

4. Display function:setting current display,action current display and each line voltage main display(voltage display need ask us when give me the order)

 

5. Alarm function:overload alarm.

 

6. Self test function:overheating self test,microcomputer self diagnosis.

 

7. Test function:intelligent controller of operating characteristic.

 

Product Choice

Name Details
Product category Universal Type Circuit Breaker
Design code 1
Current rank (Amp) 1000A,2000A,3200A,4000A,6300A
Breaking capacity M=Standard,H=High breaking
Pole 3P,4P
Product structure C=Drawer type,G=Fix type
Controller L=Economy type,M=Intelligent,H=Communication type

Precautions

Normal Use And Installation Condition

 

1. Ambient air temperature:upper limit value not exceeding+40℃,lower limiting value not exceeding -5℃,average value not exceeding +35℃.Special orders expected.

 

2. Install address of altitude not exceeding 2000m.

 

3. Atmospheric conditions:Atmosphere relative humidity not exceeding 50% when ambient air is +40℃,it can have higher of relative humidity in the lower temperature ,the average max relative humidity is 90% in the max wet month,this month average max temperature is +25℃ at the same time ,it need to think about condensation of product’s surface which will a[[ear with the change of temperature.It need consult with my company when it exceed regulated requirements.

 

4. Level of protection:IP30.

 

5 Class of pollution:3 class.

 

6. Use classes:B classes or A classes.

 

7. Installation category:Rated operating voltage 660V(690V) and below circuit breakers and undervoltage demerters,power transformer primary coil of installation category isⅣ,other assist circuit,controller installation category is Ⅲ.

 

8. Installation condition:Breaker need according to this instruction require to install,breaker of vertical gradient not exceeding 5°(mine breaker of vertical gradient not exceeding 15°)

Related Products

News information

One Two Three Electric Co., Ltd. Excels at the 48th Moscow International Power Electronics Exhibition (ELEKTRO) Pavilion in 2023

One Two Three Electric Co., Ltd. Excels at the 48th Moscow International Power Electronics Exhibition (ELEKTRO) Pavilion in 2023"

From June 6 to 9, 2023, the 48th Moscow International Power Electronics Exhibition (ELEKTRO) Pavilion opened its doors to the public, and One Two Thre...

Ready to Go | 123 Electric 2023 Exhibition Preview

Exhibition previewTime flies, after three years of anti-epidemic efforts, remarkable results have been achieved. This year, 2023, trade flows will vas...

The Difference Between Schneider Low-Voltage Electrical Products and Chinese Brand Products

First of all, Schneider's low-voltage products include circuit breakers, switches, contactors, relays, etc., which are basically world famous brands.S...

How to Select the Current of Dual Power Transfer Switch

In the design of a dual power transfer switch, the most important is the current control module (TCM), because the current is not strong enough to mee...